menutop
Copely Developments Logo
home
profile
update
event
contact
order
products
menubot
--- home codeflex coplexel codeflat pvc safestrip eurolon technical data ---
--
Previous | Next
Acrobat versionAdobe Acrobat version available

SUPRENE FIRST AID FIRE REEL HOSE - FRH 3169 series

photo

Special Features

  • Abrasion resistance - excellent
  • Made from Cadmium free materials
  • Resistance to a wide range of chemicals (see Chemical Resistance Table)
  • Outstanding U.V. / Ozone resistance
  • Silicone free
  • Ageing - outstanding resistance
  • Good flexibility


suitability
application

General Description

Suprene First Aid Fire Reel Hose is yet another quality product to be borne out of our long term materials and hose technology development.

We have continued to exploit the benefits of Rubber and P.V.C. to produce a Rubber P.V.C. Alloy (T.P.E.). This innovative step has resulted in the introduction of Codeflex Suprene First Aid Fire Reel hose.

This addition to the Codeflex Suprene range feels and looks like rubber without some of the negative aspects. As you will find from information given overleaf, our Codeflex Suprene Fire Reel Hose exceeds the requirements laid down by BS.3169 Class B, Type 1 specification in all areas.

Codeflex Suprene Fire Reel Hose has a a black inner with a distinct "Fire Red" outer in two sizes, 19mm and 25mm bore.

Print identification e.g.: "C.D. logo, BS.3169 : 1986 B1/19mm/11-92/15 BAR PATENT 0036674, DATE CODED"

Technical Data

CODEFLEX SUPRENE FIRST AID REEL HOSE FRH 3169
(U.K. And European Sizes)

Product Ref
Size (mm)
Weight per coil
kgs
Working pressure
Burst pressure
I.D.
O.D.
3:1 Safety Factor
FRH19 19 28 14.00 15 bar 60 bar
FRH25 25 36 19.99 15 bar 62 bar

Stock Lengths

19mm: 30.5mt*, 35mt, 36.6mt, 45mt, 60mt, 92mt and 100mt.
25mm: 25mt, 30.5mt* and 35mt.

Relevant Test Specification
BS 3169 Requirements
CDL Fire Reel Hose Test Result
Dimension & Tolerance
BS 5173 101.1
Bore Lining 19mm+/-0.75mm 25mm+/-0.75mm
Thickness Cover 2.0mm min
Cover Thickness 1.5mm min
Thickness variation not to exceed 15% of mean thickness.
Concentricity between inside and outside dia not to exceed 2.0mm
+0.30mm -0 13mm
2.0mm min.
1.5mm min.
Controlled within 10% maximum
Controlled within 0.5mm
Maximum Mass
(weight of hose)
19mm - 0.75kgs/m 25mm - 0.90kgs/m
0 50kgs/m (max) 0.70kgs/m (max)
Physical Properties of Lining & Cover
BS 903 PT A2
Tensile Strength & Elongation at Break
Tensile not less than 6 0 MPa Elong @ break - not less than 250%
13.7MPa
460%
BS 903 PT A19 Tensile Strength & Elongation at Break
After accelerated ageing 96hrs @ 70°C shall not vary from unaged values by more than +10% - 30%
13.6MPa (-1%)
385% (-16%)
BS2782 Methods 465A & 465B Loss in Mass on Heating Cover not greater than 4% (both methods)
465A - 0.66% 465B - 0.56%
BS 5173 103.1 Adhesion
Between lining and reinforcement Between layers of reinforcement
Between cover and reinforcement Not less than 1.75kN/m
Only the lining to outer cover separable
both sides greater than 3.5 kN/m
BS 5173 102.1 Hydrostatic Requirements
Change in dia at 15 bar +7% -5%
Change in length at 15 bar +12%-6% Burst Pressure 48 bar
+4.28% +4.72%
-0.20% 0%
60 bar 62 bar
BS 3169 Appendix A Bend Test Major axis shall not increase more than 9%
+6% +7%
BS 5173 106.3 @ 40°C Resistance to Ozone of Hose Cover
Satisfies the requirements of clause 7.5
BS 3169 Appendix B Kink Test
Satisfies the requirements of clause 7.6
BS 3169 Appendix C Resistance to Hot Surfaces
Satisfies the requirements of Class B Hoses described in clause 7.7
BS 2782 Part 1 Method 141A Fire Retardency Rating
CDL Fire Hoses have a CO1 of 25% 02



© Copely Developments Ltd - Thurmaston Lane - Leicester - LE4 7HU - England
Phone: 44 116 276 5881 - Fax: 44 116 246 0117
Email: info@copely.com